GE Telaire Duct Mount CO2 Transmitter

GE Telaire T8031 CO2 Duct Mount Transmitter is the smallest package available designed to be installed in HVAC return air ducts. The size of the board and the dimensions of the case have been optimized and mimized to be small enough to place the transmitter in small return air ducts, yet still work as well, if not better then similar products. The Ventostat T8031 product offers a sleek design, a simple analog output, and it is easy to install. The transmitter includes mounting hardware and installation instructions. 

Applications: T8031 CO2 transmitters can be used in a broad range of applications including air quality monitoring in buildings.CO2concentration levels in buildings are monitored to provide an indication of occupancy and to drive a ventilation control strategy. An effective DCV (Demand Controlled Ventilation) strategy will conserve energy and maintain indoor air quality.

Quantity

$198.61
Tax /GST included

GE Telaire T8041 is based on the absorption of light in a gold-plated reflective light pipe or waveguide diffusion gas chamber. A gas permeable PTFE filter prevents particulate and water contamination of the sensor. Light is absorbed in proportion to the CO2concentration and the remaining light is measured and converted into an analog signal.

Features:

• One of the smallest in-duct CO2 transmitters on the market

• Simple installation (mounting hardware and instructions included)3

• Ideally suited for OEM manufacturers that must accommodate smaller < 6 in (15.2 cm) HVAC return air ducts.

• Offers standard 0-10 volt output

• Patented absorption infrared/gas sensing engine provides high accuracy in a compact, low- cost package

• Patented ABC Logic™ self-calibration system eliminates the need for manual calibration in   most applications

• Gas permeable, water-resistant diffusion filter prevents particulate and water contamination of the sensor

100 Items

Data sheet

Manufacturer
Telaire by GE (General Electric)
Model
T8031
Measuring Range
0-2000 ppm factory calibrated
Accuracy
±40 ppm +3% of reading @ 22ºC
Response Time
Three minutes typical for 90% step change at low duct speeds
Operating Conditions
Temperature: 0ºC to 50ºC (32ºF to 122ºF)
Temperature Dependance
0.2% of full scale per ºC
Duct Air velocity
0 to 1500 ft/min (0-450 meter/min)
Power Supply
18 to 30 VAC RMS, 50/60 Hz or 18 to 42 VDC, polarity protected
Power Consumption
Typical values (1.65 watts peak, 0.65 watts avg. @ 42 VDC)
Calibration
Will be provided at no extra cost, valid for 1 year
Dimension
Length: 3.83 in (9.72 cm) + 0.74 in (1.87 cm) mounting tab Width: 1.17in (2.97 cm) Height: 0.94 in (2.38 cm)
Weight
12 months manufacturer warranty