GE Telaire T5100, CO2 Transmitter,Carbon Dioxide Transmitter,GE Telaire CO2 Transmitter,CO2 Sensor
GE Telaire T5100, CO2 Transmitter,Carbon Dioxide Transmitter,GE Telaire CO2 Transmitter,CO2 Sensor

GE Telaire T5100 CO2 Transmitter

GE Telaire T5100 CO2 Transmitter series is a minimal effort, high performing CO2 transmitter for the Building controls advertise. It works consistently with building mechanization frameworks and enables you to just and adequately control natural air. Request controlled ventilation utilizing CO2 sensors prevents energy losses from over-ventilation while keeping up indoor air quality.

Applications: HVAC, Greenhouse, Landfill gas, Cofined space, Marine vessels, Ventilation, Management, Mining, cellar & gas stores, Buildings, Bus, Railway waiting halls, Schools, Library, Trains, Hospitals, Office, Subway.


Quantity

$169.57
Tax /GST included

Features:

• Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low cost package.

• Patented ABC Logic™ self-calibration system eliminates the need for manual calibration in most applications.

• Lifetime CO2 calibration guarantee when using ABC Logic™.

• Mounting plate with two-piece terminal blocks provide quick, easy wiring.

• Gas permeable, water resistant CO2 diffusion filter prevents particulate and water contamination of the sensor.

• Sensors are shipped factory calibrated.

• Modern enclosure.

• Low-cost.

• Reliable (20 years of low-cost infrared sensor manufacturing).

• Available output options: Voltage 0-10V or 0-5V (jumper selectable) Or current 4-20 mA.

• UIP software compatible for customizations.

100 Items

Data sheet

Manufacturer
Telaire by GE (General Electric)
Model
T5100
Measuring Range
0 to 2000 ppm
Accuracy
± 30 ppm or 3% of the reading shown,whichever is higher*
Output
0 to 5 V, or 0 to 10 V jumper selectable (100 OHMS output impedance) Or 4 to 20 mA (RL maximum 500 Ohms)
Signal Update
Every 5 seconds
Operating Range
32°F to 122°F (0°C to 50°C)
Temperature Dependance
0.2% FS per °C (±0.11% per °F)
Storage Conditions
-40°F to 158°F (-40°C to 70°C)
Sensing Method
Non-dispersive infrared (NDIR) absorption gold plated optics Patented ABC Logic self Calibration algorithm
Power Supply
18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected
Power Consumption
Typical 0.7 W at normal voltage of 24V AC RMS
Flammability Classification
UL94 5VA
Warranty
24 months manufacturing warranty