ACE INSTRUMENTS make Digital Differential Pressure Indicator are digital readout differential pressure monitors designed for measuring the room pressure inside Pharma clean rooms, hospital operation theatres & isolation rooms. Differential Pressure Indicators are part replacement for the analog differential pressure gauges & are easy to read with crystal clear 4 digit LED Display. It comes with built in sensor & also a buzzer alarm with acknowledgement facility for process violation alert in case of room pressure exceeding set limits. 

Applications: Pharmaceutical Clean Rooms,Laminar Air Flow Cabinets,HVAC,Biosafety Cabinets,AHUs etc.

Select Pressure Range
Options
Quantity

$131.16
Tax /GST included

Differential Pressure Indicators are part replacement for the Analog Magnehelic Gauges & are easy to use with clear 4 digit LED Display. It comes with built in sensor & also a buzzer alarm with acknowledgement facility for process violation alert.

Salient Features include Unit Conversion at the press of a key between mm.W.C.& Pascals integrated buzzer alarm for set point violation, Offset provision to meet Audit requirements, analog 4-20mA Output, 42 mm depth for Clean Room Modular Wall Fitment & RS 485 Modbus communication for BMS/SCADA/PLC integration.

98 Items

Data sheet

Manufacturer
ACE Instruments
Model
AI-DP1
Measuring Range
Standard -50.0 to +50.0 mm.W.C./-500 to +500 Pascals (Contact store for any other range)
Accuracy
± 0.5% of Full Scale.
Output
Optional 4–20 mA Isolated
Maximum Over Pressure
2 Times the rated pressure
Power Supply
24 Volts D.C. Typical
Construction
Aluminium LM-6 Powder Coated Body with Flush Bezel Fitment; Water Splash Proof Polycarbonate Front Sticker
Communication
Isolated RS485 Modbus Protocol (optional)
Sensor Type
Integrated High Speed Differential Pressure Sensor
Buzzer
Built in Buzzer Alarm for Process Violation Alert
Connection
Instrument Enclosure is in 75x70x40 mm. (Wx Hx D) with 2 Nos. Hose Nipples of 4mm. Stainless Steel at the Back
Medium
Air or Gases ( Non Corrosive )
Size
Instrument Enclosure is in 75x70x40 mm. (Wx Hx D) with Basic Imported Sensor ; Standard 4 ½′′ Diameter Magnahelic Gauge Size 30 mm.
Calibration
Will be provided at no extra cost valid for 1yr traceable to Electronic Test & Development Centre