E+E Elektronik EE850 CO2, Humidity and Temperature Duct Sensor
277192
E+E Elektronik EE850 CO2, Humidity and Temperature Duct Sensor is a device which measures of CO2 levels, relative humidity (RH), and temperature (T) in various applications, particularly in demand-controlled ventilation and building automation systems. This Temperature Humidity Sensor functional design installing it into a duct, where a controlled amount of air flows through the divided probe to reach the CO2 sensing cell inside the transmitter enclosure.
Applications : Building automation, HVAC Systems, Clean Rooms, Greenhouses, Commercial Buildings.
Products related to this item
-
₹13,590.00 – ₹20,576.00
(GST 18% Exclusive)
Siemens QFA3171 Temperature and Humidity Sensor
-
₹15,995.00 – ₹16,750.00
(GST 18% Exclusive)
Siemens QFM3160 Duct Relative Humidity Temperature Sensor
-
₹11,760.00
(GST 18% Exclusive)
Honeywell H7080B3273 Duct Mount Temperature and Humidity Sensor
-
₹11,200.00
(GST 18% Exclusive)
Honeywell H7080B3103 Temperature Humidity Sensor
E+E Elektronik EE850 CO2, Humidity and Temperature Duct Sensor is highly resistant to pollution, and ensures outstanding long-term stability. E+E dual wavelength NDIR CO₂ working principle which reduces ageing effects, is highly insensitive to pollution & offers outstanding long term stability. It comes with a Optional passive temperature sensor and Easy user configuration and adjustments design. It comes with the PCS10 Product Configuration Software.
Features E+E Elektronik Temperature Humidity CO2 duct sensor
- EE850 CO2 Temperature and Humidity Transmitter comes with configuration software
- Temperature humidity sensor protection class-IP65
- The RS485 interface with Modbus RTU or BACnet MS/TP protocol enables the transmission of additional parameters
Additional information
Manufacturer | Elektronik |
---|---|
Model No | EE850 |
Measuring Parameters | CO2, Temperature, Humidity |
CO2 range | 0 to 2 000 / 5 000 / 10 000 ppm |
Accuracy | < ±(50 ppm + 2 % of measured value) < ±(50 ppm + 3 % of measured value) < ±(100 ppm + 5 % of measured value) |
Temperature Range | -20…+60 °C (-4…+140 °F) |
Accuracy | ±0.3 °C (±0.5 °F) |
Humidity Range | 0 to 95 % RH |
Accuracy | ±3 %RH (20…80 %RH) |
Measurement principle | Dual wavelength non-dispersive infrared technology |
Power Supply | 15 to 35 VDC |
Cable gland | M16 x 1.5 |
Temperature Dependance | Typ. ± 0.2% of reading per °C or ± 2ppm per °C, whichever is greater, referenced to 25°C |
Current consumption | 15 mA + output current |
Response Time | < 50s, 10 sec |
Material | Polycarbonate |
Ratings | IP65 |
Electrical Connection | Screw terminals max. 2.5 mm2 |
Electromagnetic compatibility | EN 61326-1, EN 61326-2-3 |
Software | PCS10 Product Configuration Software |
Accessories | Connection cable M12x1 socket, E+E Product Configuration Software, Power supply adapter, Protective cap for M12 plug, Protective cap for M12 socket, USB configuration adapter |